What does BMECRA31210 MS and NS flashing green with no Run light indicate? (BMECRA31210, BMXCRA31210)

까망늑대 2025. 11. 7. 14:51
반응형

What does BMECRA31210 MS and NS flashing green with no Run light indicate? (BMECRA31210, BMXCRA31210)

( BME(X)CRA31210 MS와 NS가 녹색으로 깜박이면서 RUN LED가 켜지지 않는 이유는 무엇입니까?)

 

Issue

When trying to set up X80 or Quantum EIO drops, cannot get a drop to come up and be recognized. 
( X80 또는 Quantum EIO 드롭을 설정하려고 할 때 드롭이 나타나거나 인식되지 않습니다.)


Product line
Modicon X80 IO, Modicon M580, Quantum EIO

Resolution

If it does not recover after power up, this can also be caused be either the M580 not physically seeing the CRA (check cabling) or the incorrect CRA selected in the project configuration (there are multiple CRA choices (for X80 IO), make sure the configuration matches the hardware).
( M580이 CRA를 물리적으로 인식하지 못하거나(케이블 연결 확인) 프로젝트 구성에서 잘못된 CRA를 선택했기 때문일 수 있습니다.)


In the M580 Security settings, TFTP, EIP and DHCP / BOOTP need to be Enabled
( M580 보안 설정에서 TFTP, EIP 및 DHCP/BOOTP를 활성화해야 합니다. )


If in the Security settings you have activated Access Control, you will need to activate(select) TFTP and EIP in order to communicate to the CRA modules.

( 보안 설정에서 접근 제어를 활성화한 경우, CRA 모듈과 통신하려면 TFTP와 EIP를 활성화(선택)해야 합니다. )

The CRA network should be isolated but another reason this might happen is if another module/device has the same IP address that the CRA module auto-assigns.

( CRA 네트워크는 격리되어야 하지만, 다른 모듈/장치가 CRA 모듈이 자동으로 할당한 IP 주소와 동일한 IP 주소를 사용하는 경우에도 이러한 문제가 발생할 수 있습니다.)


만약 Topo Address가 틀린 경우는 MS가 적색으로 점멸(Blinking) 하게 됩니다.

 